The current transformers of the PCE-LCTB 86/40 (45) series are used when alternating currents in circuits are too high to be detected directly by measuring devices. The current transformer converts the primary current into a proportionally reduced secondary current, which can be processed by a measuring device. In addition, the current transformer protects connected measuring devices from excessive voltages. The current transformers of the PCE-LCTB 86/40 (45) series can detect primary currents from 50 A to 1000 A depending on the version and convert these into a 1 A or 5 A secondary current. In addition, between the accuracy classes, 1 / 0.5 / 0.2 / 0.2s can be selected.
– Primary winding (input): 50 A … 1000 A
– secondary (output): 1 A / 5 A
– System voltage: max. 720 V
– Accuracy grades: 0.2s / 0.2 / 0.5 / 1
– Frequency: 50 Hz
– IEC / EN 60044-1, BS 3938, IS 2705-1 standards
– Easy installation
– Compact dimensions
Primary winding (input): 50 A … 1000 A
Secondary winding (output): 1 A, 5 A
Accuracy classes: 0.2s / 0.2 – for laboratory and performance measurements, 0.5 – for accurate measurements, 1 – for ordinary measurements for analog gauges
Depth: 45 mm
Width: 86 mm
Hole diameter: Ø 36 mm
Busbar: 40x10mm, 2x30x15mm
Standards: IEC / EN 60044-1, BS 3938, IS 2705-1
Housing: 10% glass fiber reinforced polycarbonate, flame retardant according to UV94V-0
Connections: 2 connections on each side
Heat class: E (to 120 ° C)
System voltage: Max. 720 V
Rated capacity: 1.5 VA … 30 VA
Ambient temperature: -20 ° C … +45 ° C
Storage temperature: -50 ° C … +80 ° C
Thermal short-circuit current (I th): 40 x In
Dynamic short-circuit current (I dyn): 2.5 x I th
Safety factor: 5
รีวิว
ยังไม่มีบทวิจารณ์