For measuring system parameters of single-phase networks /
optional pulse output and RS485 interface / IP65 protected front side
optional pulse output and RS485 interface / IP65 protected front side
The Power Meter PCE-N30P can determine the most important system parameters of a single-phase network. Based on the current and voltage, the Power Meter PCE-N30P calculates the apparent, active and reactive power, as well as the phase difference angle and the power factor. The Power Meter can also determine the average power for a 15 minute period and the average voltage for a 10 minute period. By using transducers, the measuring range of the Power Meter can be extended. The settings can be adjusted via the buttons on the front site of the PCE-N30P. It is also possible to program threshold values, which trigger a signal through the two alarm outputs. In addition, the colour of the display can be changed, depending on the actual measuring value. The PCE-N30P is available with different measuring units, outputs and power supplies. You can select the particular parameters further below.
– measuring and indication of 16 different parameters
– IP 65 protection on the front
– three-coloured display
– two alarm outputs
– 4 buttons on the front
– optional RS485 interface, OC pulse output, changeover relay, analogue output
– IP 65 protection on the front
– three-coloured display
– two alarm outputs
– 4 buttons on the front
– optional RS485 interface, OC pulse output, changeover relay, analogue output
Technical specifications | |
Input | Current: 0.02 … 6 A Voltage: 0 … 480 V Frequency: 45.00 … 100.00 Hz |
Accuracy | current, voltage, frequency: 0.2 % active, apparent, reactive power: 0.5 % power factor: 0.5 % phase difference angle: 1 % active, reactive energy: 0.5 % |
Display | 5-digits, 7-segments, LED, three-coloured |
Power consumption | 6 VA |
Outputs | 2 closing relays 250 V / 0.5 A |
Additional outputs (selectable) | 2 changeover relays 250 V / 0.5 A RS485 interface analogue output (4 … 20 mA / 0 … 10 V) open collector pulse output |
Environmental conditions | During operation: -25 °C … 55 °C / 25 … 95 % RH During storage: -33 °C … +70 °C / 25 … 95 % RH |
Dimensions | 96 x 48 x 93 mm |
Panel cutout | 92 x 45 mm (according to DIN standard) |
Power supply (wählbar) | 85 … 253 V AC/DC 20 … 40 V AC/DC |
Protection class | Front: IP 65 |
Weight | < 200 g |
Mounting | Mounting clips with screws, Connection via screw terminals (connection plan on the housing) |
Standard specification | EN 61010-1 CAT III 600 V |